Better Smarter Faster

Follow us: Call us: 888 518 8086

spec sheet header

Specification Sheet

Lake Cable Part #: V167

Description: 16 AWG 7 conductor 7 strand bare copper with polyvinylchloride and nylon insulation, unshielded with an overall PVC jacket 600V control tray cable, approved for use in SUN RES DIR BUR OIL RES I 90°C applications.

1. Conductor
1.1. AWG Size & Stranding: 16 AWG 7 Strands Class B
1.2. Material: Annealed Bare Copper
1.3. Conductor Count: 7 Conductors

2. Insulation
2.1. Material: Polyvinylchloride & Nylon
2.2. Wall Thickness: 0.015” PVC & 0.005” Nylon
2.3. Color Code: Method 1, Table E-2

3. Assembly
3.1. Lay Length: Per UL Standard 1277
3.2. Fillers: N/A
3.3. Binder: N/A
3.4. Shield: N/A
3.5. Drain Wire: N/A

4. Jacket
4.1. Material: Polyvinylchloride
4.2. Wall Thickness: 0.045”
4.3. Diameter: 0.385”
4.4. Color: Black
4.5. Ripcord: Yes
4.6. Cold Bend Rating: -40°C
4.7. Weight: 114 lbs./Mft.

5. Markings
5.1. Type: Cable shall be permanently identified via surface inkjet print
5.2. Legend: LAKE CABLE E208309 16AWG 7C (UL) TC-ER PVC/NYLON 600V 90’C DRY/WET PVC JACKET SUN RES DIR BUR OIL RES I FT4 “ROHS”
5.3. Footage Markers: Yes

6. Standards
6.1. Refer to NEC (NFPA 70) article 1277 for installation guidelines
6.2. Cable is suitable for use in Class I Division II hazardous locations
6.3. UL listed as Type TC-ER per UL Standard 1277 for tray cables
6.4. UL approved for Direct Burial, Sunlight and Oil I Resistant applications
6.5. Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
6.6. Meets ICEA S-73-532, where applicable
6.7. All materials used in the manufacture of this cable are RoHS compliant
6.8. Made in the USA

ALL SPECIFIED PARAMETERS ARE NOMINAL AND SUBJECT TO VERIFICATION