Copper Price 4/26/2024 4.6215

AVP162VANT-07

16 AWG, 2 conductor unshielded plenum rated cable constructed with stranded bare copper, Foam FEP insulation and an overall PVC jacket. Lighting and control cable for Vantage station devices and touch screens
SKU: AVP162VANT-07
 
• Cable suitable for installations under NEC (NFPA 70) article 800 and article 725 guidelines
• UL listed as CMP per UL 444 and Type CL3P per UL Standard 13
• All materials used in the manufacture of this cable are RoHS compliant
• Made in the USA
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Nominal Electrical Characteristics
Characteristic Impedance80 Ω +/- 5
Mutual Capacitance16.2 pF/ft +/-10%
DC Resistance3.99 Ω/Mft @ 20°C
Conductor
AWG & Stranding16 AWG 19 Strands Class C
MaterialAnnealed Bare Copper
Conductor Count2 Conductors
Insulation
MaterialFoamed Fluorinated Ethylene Propylene
Nominal Wall Thickness0.008”
Color CodeBlack, Red
Assembly
Cable Lay Length3.00” LHL (4.0 tw/ft)
Jacket
MaterialPlenum Rated Polyvinylchloride
Nominal Wall Thickness0.014”
Nominal Diameter0.172”
ColorViolet
Nominal Weight27 lbs/Mft
RipcordYes
Markings
TypeCables permanently identified via surface inkjet print
LegendVANTAGE (801) 229-2800 E171197 16AWG 2C (UL) CMP C(UL)US OR (UL) CL3P OR 75’C FT-6 “ROHS”
Footage MarkersYes
Standards
Maximum operating voltage300V