18AWG 2PR SOL OAS 150C LL5 FPLP
SKU: L182PRS
 

18 AWG 2 PAIR SOLID BARE COPPER WIRE WITH .015" PVDF (SOLEF) INSULATION, OVERALL ALUMINUM MYLAR TAPE SHIELD WITH A 20 AWG SOLID TINNED COPPER DRAIN WIRE, OVERALL .025" PVDF (SOLEF) RED JACKET.

(UL) FPLP 150'C "ROHS"

CC: BLACK & RED, WHITE & GREEN.

PRINT: ALSO CLASSIFIED NYC CERT FIRE ALARM

E-Z STRIP LL5 FT-6

This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.

Products specifications

Conductor

AWG Size & Stranding:
18 AWG Solid
Material:
Bare Copper Wire
Conductor Count:
2 Pair
AWG & Stranding:
18 Awg Solid

Insulation

Material:
Polyvinylidene Fluoride
Wall Thickness:
.015"
Color Code:
Black & Red, White & Green

Assembly

Pair Lay Length:
4.50” LHL (2.66 Tw/Ft)
Cable Lay Length:
4.50” LHL (2.66 Tw/ft)
Shield:
Aluminum Mylar Tape Shield - 100% Coverage
Drain Wire:
20 Awg 7 Strand Tinned Copper Wire
Nominal Lay Length:
4.50”

Jacket

Material:
Polyvinylidene Fluoride
Wall Thickness:
.025"
Diameter:
0.2854”
Color:
Red
Ripcord:
No
Weight:
50 lbs per mft
Nominal Diameter:
.282"

Markings

Type:
Permanent Inkjet Surface Print
Legend:
LAKE CABLE L182PRS E171203 18AWG 2PR SHIELDED (UL) FPLP 150’C FT-6 ALSO CLASSIFIED NYC CERT FIRE ALARM E-Z STRIP LL39 “ROHS COMPLIANT” MADE IN USA
Footage Markers:
Yes

Standards

Maximum operating voltage:
300V
Operating Temperature Range:
-40C TO 150C

Approvals

Approvals List:

• Cable suitable for installation under NEC (NFPA 70) article 760 guidelines
• UL listed as type FPLP 150°C per UL standard 1424
• Classified NYC Certified Fire Alarm LL39
• Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• Cable is REACH compliant per Regulation (EC) No 1907/2006 (240) Updated January 23, 2024
• Maximum Operating Voltage: 300V
• Made in the USA
• Operation Temp -40°C to 150°C
• WARNING: This product may contain chemicals, such as Vinyl Chloride, known to the state of California to cause cancer. For more information, go to www.P65Warnings.ca.gov. Wash hands after handling.

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels