Copper Price 06/13/2025 4.7425
18AWG 2PR SOL OAS 150C LL5 FPLP
SKU: L182PRS
 

18 AWG 2 PAIR SOLID BARE COPPER WIRE WITH .015" PVDF (SOLEF) INSULATION, OVERALL ALUMINUM MYLAR TAPE SHIELD WITH A 20 AWG SOLID TINNED COPPER DRAIN WIRE, OVERALL .025" PVDF (SOLEF) RED JACKET.

(UL) FPLP 150'C "ROHS"

CC: BLACK & RED, WHITE & GREEN.

PRINT: ALSO CLASSIFIED NYC CERT FIRE ALARM

E-Z STRIP LL5 FT-6

This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor
AWG Size & Stranding18 AWG Solid
MaterialBare Copper Wire
Conductor Count2 Pair
AWG & Stranding18 Awg Solid
Insulation
MaterialPolyvinylidene Fluoride
Wall Thickness.015"
Color CodeBlack & Red, White & Green
Assembly
Pair Lay Length4.50” LHL (2.66 Tw/Ft)
Cable Lay Length4.50” LHL (2.66 Tw/ft)
ShieldAluminum Mylar Tape Shield - 100% Coverage
Drain Wire20 Awg 7 Strand Tinned Copper Wire
Nominal Lay Length4.50”
Jacket
MaterialPolyvinylidene Fluoride
Wall Thickness.025"
Diameter0.2854”
ColorRed
RipcordNo
Weight50 lbs per mft
Nominal Diameter.282"
Markings
TypePermanent Inkjet Surface Print
LegendLAKE CABLE L182PRS E171203 18AWG 2PR SHIELDED (UL) FPLP 150’C FT-6 ALSO CLASSIFIED NYC CERT FIRE ALARM E-Z STRIP LL39 “ROHS COMPLIANT” MADE IN USA
Footage MarkersYes
Standards
Maximum operating voltage300V
Operating Temperature Range-40C TO 150C
Approvals
Approvals List

• Cable suitable for installation under NEC (NFPA 70) article 760 guidelines
• UL listed as type FPLP 150°C per UL standard 1424
• Classified NYC Certified Fire Alarm LL39
• Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• Cable is REACH compliant per Regulation (EC) No 1907/2006 (240) Updated January 23, 2024
• Maximum Operating Voltage: 300V
• Made in the USA
• Operation Temp -40°C to 150°C
• WARNING: This product may contain chemicals, such as Vinyl Chloride, known to the state of California to cause cancer. For more information, go to www.P65Warnings.ca.gov. Wash hands after handling.

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels