• Refer to NEC (NFPA 70) article 336 for installation guidelines
• Cable is suitable for use in Class I Division 2 hazardous locations
• UL listed as Type TC-ER per UL Standard 1277 for tray cables
• UL approved for Direct Burial, Sunlight and Oil I & II Resistant applications per UL 1277
• Individual conductors pass UL VW-1 flame test, rated THW-2/VW-1
• UL listed as Type STOOW per UL Standard 62 for flexible cords
• UL approved for Sunlight, Oil and Weather Resistant & Water Submersed applications per UL 62
• Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR
• Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• Cable is REACH compliant per Regulation (EC) No 1907/2006 (240) Updated January 23, 2024
• Made in the USA
• For tray cable: 76 amps, Ampacity based on values published in NEC Table 310.16. Value based on wire insulations rated 90°C in ambient temperature of 30°C and Adjustment Factors for more than 3 current-carrying conductors per table 310.15(b)(16)
• For portable cords: 48 amps, Ampacity based on values published in NEC Table 400.5(A)(1). Values based on wire insulations rated for 90C in ambient temperature of 30C and Adjustment factors for more than 3 current-carrying conductors per table 400.5(A)(3).