16 AWG 2C 7STR BC OAS PVC/PVC (UL) ITC/PLTC/CL3 300V 105C
SKU: T162S
 

16 AWG 1 PAIR 7 STRAND BARE COPPER WIRE WITH .016" PVC INSULATION, OVERALL ALUMINUM MYLAR TAPE SHIELD WITH AN 18 AWG 7 STRAND TINNED COPPER DRAIN WIRE, OVERALL .035" BLACK PVC JACKET.
(UL) ITC SUN RES OR PLTC OR CL3 FT-4 "WET LOCATIONS" "ROHS COMPLIANT" MADE IN USA
CC: BLACK & WHITE
RIPCORD: YES
FOOTAGE MARKERS: YES

This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.

Products specifications

Conductor

AWG Size & Stranding:
16 AWG 7 Strands Class B
Material:
Annealed Bare Copper
Conductor Count:
2 Conductors

Insulation

Material:
Polyvinylchloride
Wall Thickness:
0.016”
Color Code:
Black, White

Assembly

Cable Lay Length:
2.75” LHL (4.36 Tw/Ft)
Cable Binder:
N/A
Cable Shield:
Aluminum Mylar – 100% Coverage
Cable Drain Wire:
18 AWG 7 Strand Tinned Copper

Jacket

Material:
Polyvinylchloride
Wall Thickness:
0.035”
Diameter:
0.253”
Color:
Black
Ripcord:
Yes
Weight:
44 Lbs/Mft

Markings

Type:
Cable shall be permanently identified via surface inkjet print
Legend:
LAKE CABLE E171202 16AWG 2C SHLD (UL) PLTC OR (UL) ITC OR (UL) CL3 105’C SUN RES DIR BUR FT-4 “ROHS”
Footage Markers:
Yes

Electrical Characteristics

Impedance:
49 Ω ± 10%
Capacitance:
35 pF/ft ± 10%
DC Resistance:
4.13 Ω/Mft. @ 20’C

Standards

Maximum Voltage:
300V

Approvals

Approvals List:

• UL listed as type PLTC & CL3 per UL standard 13 and as type ITC per UL standard 2250
• Cable is suitable for use in Class I Division 2 hazardous locations
• Cable is UL approved for Sunlight Resistant Applications.
• Meets IEEE 1202 flame test
• Recommended Operating Voltage: 300V RMS
• Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• Cable is REACH compliant per Regulation (EC) No 1907/2006 (240) Updated January 23, 2024
• Made in the USA
• WARNING: This product may contain chemicals, such as Vinyl Chloride, known to the state of California to cause birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov. Wash hands after handling.

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels