Copper Price 4/25/2024 4.5700

V183-QR

18 AWG 3 conductor 7 strand bare copper with polyvinylchloride and nylon insulation unshielded with an overall PVC jacket 600V control tray cable, PLTC, NPLF & FPL, approved for use in SUN RES DIR BUR OIL RES I 90°C applications.
SKU: V183-QR
 
• Cable is suitable for use in Class I Division II hazardous locations
• UL listed as Type TC-ER per UL Standard 1277 for tray cables and Quad Rated TC, PLTC, NPLF & FPL
• UL approved for Direct Burial, Sunlight and Oil I Resistant applications
• Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
• Meets ICEA S-73-532, where applicable
• All materials used in the manufacture of this cable are RoHS compliant
• Made in the USA
• Refer to NEC (NFPA 70) article 1277 for installation guidelines
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor
AWG Size & Stranding18 AWG, 7 Strands Class B
MaterialAnnealed Bare Copper
Conductor Count3 Conductors
Insulation
MaterialPolyvinylchloride & Nylon
Wall Thickness0.015” PVC & 0.005” Nylon
Color CodeMethod 1, Table E-2
Assembly
Lay LengthPer UL Standard 1277
FillersN/A
BinderN/A
ShieldN/A
Drain WireN/A
Jacket
MaterialPolyvinylchloride
Wall Thickness0.045”
Diameter0.274”
ColorBlack
RipcordYes
Cold Bend Rating-40°C
Weight44 lbs./Mft.
Markings
TypeCable shall be permanently identified via surface inkjet print
LegendLAKE CABLE E208309 18AWG 3C (UL) TC-ER 600V PLTC NPLF FPL PVC/NYLON 600V 90’C DRY/WET PVC JACKET SUN RES DIR BUR OIL RES I FT4 “ROHS” MADE IN USA
Footage MarkersYes

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels