Conductor |
AWG Size & Stranding | 18 AWG, 7 Strands Class B |
Material | Annealed Bare Copper |
Conductor Count | 37 Conductors |
Insulation |
Material | Polyvinylchloride & Nylon |
Wall Thickness | 0.015” PVC & 0.005” Nylon |
Color Code | Method 1, Table E-2 |
Assembly |
Lay Length | Per UL Standard 1277 |
Fillers | N/A |
Binder | Clear Mylar |
Shield | Aluminum/Mylar Tape - 100% coverage |
Drain Wire | 20 AWG, 7 Strand Tinned Copper |
Jacket |
Material | Polyvinylchloride |
Wall Thickness | 0.060” |
Diameter | 0.751” |
Color | Black |
Ripcord | Yes |
Cold Bend Rating | -40°C |
Weight | 393 lbs./Mft. |
Markings |
Type | Cable shall be permanently identified via surface inkjet print |
Legend | LAKE CABLE E208309 18AWG 37C SHIELDED (UL) TC-ER PVC/NYLON 600V 90’C DRY/WET PVC JACKET SUN RES DIR BUR OIL RES I FT4 “ROHS” |
Footage Markers | Yes |
Approvals |
Approvals List | • Refer to NEC (NFPA 70) article 1277 for installation guidelines • Cable is suitable for use in Class I Division II hazardous locations • UL listed as Type TC-ER per UL Standard 1277 for tray cables • UL approved for Direct Burial, Sunlight and Oil I Resistant applications • Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements • Meets ICEA S-73-532, where applicable • All materials used in the manufacture of this cable are RoHS compliant • Made in the USA |