Copper Price 04/30/2025 4.5070
6 AWG 3C 266STR BC + (3) UNINS GND SCU XLPE/PVC (UL) TC-ER OR VFD 1KV 90C
SKU: VFDX63SCU
 

6 AWG 3C 266 STRAND BARE COPPER WIRE WITH .045" XLPE INSULATION + (3) #12 AWG 65 STRAND UNINSULATED BARE COPPER GROUND WIRES, FILLERS AND OVERALL CLEAR MYLAR WRAP TAPE, OVERALL .005" HELICALLY APPLIED BARE COPPER TAPE SHIELD, OVERALL .060" BLACK PVC JACKET.
LEGEND: (UL) TC-ER XHHW-2/VW-1 600V 90'C DRY/WET SUN RES DIR BUR FT4 OR FLEXIBLE VFD SERVO MOTOR CABLE 1KV 90'C DRY/WET "ROHS COMPLIANT" MADE IN USA
CC: METHOD 1, TABLE E-2
RIPCORD: YES
FOOTAGE MARKERS: YES

This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.
Products specifications
Attribute nameAttribute value
Conductor
AWG Size & Stranding6 AWG 266 Strands Class K
MaterialAnnealed Bare Copper
Conductor Count3 Conductors
Insulation
MaterialCross-linked Polyethylene
Wall Thickness0.045"
Color CodeMethod 1, Table E-2
Assembly
Ground(3) Uninsulated – 12 AWG 65 Strand Bare Copper
Fillers"Non-Hygroscopic Polypropylene - As required for a circular cross-section"
BinderClear Mylar
Shield0.005” Helical Bare Copper Tape – 20% minimum overlap
Drain WireN/A
Jacket
MaterialPolyvinylchloride
Wall Thickness0.060”
Diameter.744” ± 0.060”
ColorBlack
RipcordYes
Cold Bend Rating-40°C
Weight548 lbs./Mft.
Markings
TypeCable shall be permanently identified via surface inkjet print
LegendLAKE CABLE E208309 6AWG 3C (UL) TC-ER XHHW-2/VW-1 UNINSULATED GROUNDS 1000V 90C DRY/WET BARE COPPER TAPE SHIELD PVC JACKET SUN RES DIR BUR FT4 OR FLEXIBLE VFD SERVO MOTOR CABLE XHHW-2 CDRS 1000V 90C DRY/WET “ROHS COMPLIANT” MADE IN USA
Footage MarkersYes
Approvals
Approvals List

• Refer to NEC (NFPA 70) article 336 for installation guidelines
• Cable is suitable for use in Class I Division 2 hazardous locations
• UL listed as Type VFD per UL Standard 2277 for Flexible VFD Servo Motor Cables
• UL approved for Sunlight resistant applications
• Individual conductors pass UL VW-1 flame test, rated XHHW-2/VW-1
• Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
• Meets ICEA S-95-658, where applicable
• Cable meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• Cable is REACH compliant per Regulation (EC) No 1907/2006 (224) Updated June 10, 2022
• Made in the USA

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels