16 AWG 7 conductor 7 strand bare copper with XLPE insulation, an aluminum/mylar shield with a stranded tinned copper drain wire and an overall PVC jacket 600V control tray cable, approved for use in SUN RES DIR BUR 90°C applications.
SKU: VX167S
 
• Refer to NEC (NFPA 70) article 1277 for installation guidelines
• Cable is suitable for use in Class I Division II hazardous locations
• UL listed as Type TC-ER per UL Standard 1277 for tray cables
• UL approved for Direct Burial and Sunlight Resistant applications
• Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
• Meets ICEA S-73-532, where applicable
• All materials used in the manufacture of this cable are RoHS compliant
• Made in the USA
This spec is for informational purposes and subject to change. This spec may not be suitable for submission. Contact Lake Cable for non-watermark spec sheet.

Products specifications

Conductor

AWG Size & Stranding:
16 AWG 7 Strands Class B
Material:
Annealed Bare Copper
Conductor Count:
7 Conductors

Insulation

Material:
Cross-linked Polyethylene
Wall Thickness:
0.030”
Color Code:
Method 1, Table E-2

Assembly

Lay Length:
Per UL Standard 1277
Fillers:
N/A
Binder:
N/A
Shield:
Aluminum/Mylar Tape - 100% coverage
Drain Wire:
20 AWG 7 Strand Tinned Copper

Jacket

Material:
Polyvinylchloride
Wall Thickness:
0.045”
Diameter:
0.450”
Color:
Black
Ripcord:
Yes
Cold Bend Rating:
-40°C
Weight:
142 lbs./Mft.

Markings

Type:
Cable shall be permanently identified via surface inkjet print
Legend:
LAKE CABLE E208309 16AWG 7C SHIELDED (UL) TC-ER XLPE 600V 90’C DRY/WET PVC JACKET SUN RES DIR BUR FT4 “ROHS”
Footage Markers:
Yes

Remember, all of our wire can feature:

  • Short minumum runs
  • Special jacket colors including stripes
  • Custom print legends
  • Custom cable constructions
  • Custom packaging - boxes or reels
  • Custom lengths
  • Your name on package labels